Ground Fault Indicators: How they Work, Where they Fit and What to Look for

Ground Fault Indicators

In medium-voltage (MV) distribution networks, ground fault indicators (also called earth fault indicators or fault passage indicators, FPIs) help crews pinpoint single-phase-to-ground faults quickly so restoration can begin sooner. By providing a clear visual or remote signal that a fault current has passed a given location, FPIs narrow the search area, cut patrol time and reduce outage minutes.ย 

What is a Ground Fault Indicator?

A ground fault indicator is a sensing and signalling device installed on feeders, in switchgear, or on lines. During a ground fault, the device detects characteristic current/field conditions and flips a mechanical target and/or LEDs; in some models, it also transmits the event to SCADA. The concept is straightforward: mark the last healthy point upstream of the fault so crews can bracket the damaged section.

Not to be confused with GFCI (ground-fault circuit interrupter) devices used in low-voltage buildings to protect people from shock by opening a circuit at small leakage currents. FPIs are grid-operations tools; GFCIs are personal-protection devices.

How do FPIs Detect Ground Faults?

Most FPIs sense the magnetic field produced by current in the conductor. Panel-mount and underground types often employ Rogowski-coil or CT-based sensors; overhead line indicators may clamp directly to the line. In grounded systems, a fault produces a distinctive increase in current; in isolated or resonant-earthed systems, indicators often look at the vector sum (zero-sequence) and detect imbalance. Newer devices can also communicate their tripped/reset state.

Why Utilities Deploy Them?

  • Faster fault location โ€” shorter SAIDI/CAIDI and lower operating costs.
  • Fewer hazardous โ€œfault-chaseโ€ operations โ€” better crew safety.
  • Better switching decisions with remote signalling devices

Indicator Types

  • Overhead line FPIs โ€” clamp-on, highly visible targets; some add radio/cellular.
  • Underground/cable and switchgear FPIs โ€” panel-mount with LEDs/flags, sometimes dry contacts or RS-485/Modbus for SCADA.
  • Short-circuit + earth-fault combos โ€” detect phase-to-phase and phase-to-ground events.

What to Consider When Selecting a Ground Fault Indicator

  1. System grounding: solid, high-resistance, or resonant (Petersen). Sensitivity and algorithms differ; low-current PtG faults demand low pickup and sometimes directional logic.
  2. Load profile & settings: choose pickup/hold times that avoid false trips on inrush or capacitive discharge.
  3. Installation point: panel/wall mount for MV switchgear vs. line-mounted for overhead.
  4. Indication & reset: mechanical flag + high-intensity LED; reset by time, manual pushbutton or remote/command.
  5. Communications: local-only or integrated (dry contacts/RS-485) for SCADA alarms.
  6. Environment & endurance: enclosure rating (e.g., IP65), temperature range, MTBF.

Product Example: Lodestar PT2 (short-circuit and earth-fault indicator)

For readers seeking a concrete reference design, the Lodestar PT2 is a panel/wall-mount short-circuit and earth-fault indicator for 6โ€“35 kV distribution equipment. Key characteristics include: Rogowski-coil-based sensing, adjustable PtG pickup from 10 A, ultra-bright LED + mechanical flag indication, and multiple reset options (manual, time-based, external command/remote). The unit carries IP65 protection; auxiliary supply options include 110 V DC / 220 V AC-DC, with a standby lithium battery, and the stated MTBF โ‰ฅ110,000 h. These attributes align well with typical MV switchgear applications; for remote signalling/SCADA, the related PRO variant adds RS-485 (Modbus).ย 

Application Notes and Good Practice

  • Tune sensitivity to grounding scheme. Isolated or resonant-earthed networks often require lower pickups and care with non-directional devices to avoid misoperations on capacitive discharge.
  • Place indicators to โ€œbracketโ€ likely fault points. Pairing an upstream panel FPI (e.g., PT2) with downstream line devices shortens patrols.
  • Document reset logic in switching procedures. Time-reset devices should be coordinated with restoration sequencing and reclose policy.

Frequently Asked Questions (FAQs)

  1. Are ground fault indicators the same as GFCIs?

    No. FPIs (MV network tools) signal where a fault current has passed; GFCIs (building safety devices) interrupt low-voltage circuits upon small leakage to protect people from shock. Different purpose, ratings, and standards.

  2. Do indicators work in resonant-earthed (Petersen coil) systems?

    They can, but setup is more demanding. Look for high sensitivity and, where needed, directional algorithms or zero-sequence measurements; avoid promising universal performance without confirming in-network conditions.

  3. Where should I install FPIs for best results?

    At strategic points that divide the feeder into segments (e.g., incoming switchgear, key junctions/cabinets, overhead taps). This โ€œsegmentationโ€ lets crews quickly isolate the faulted span.

  4. Can I integrate an indicator with SCADA?

    Yes. Many panel-mount FPIs offer dry contacts or serial interfaces (e.g., RS-485/Modbus) to alarm the control room when a trip occurs, improving situational awareness. Check the specific modelโ€™s I/O.

  5. Whatโ€™s a good real-world example device?

    The Lodestar PT2 for 6โ€“35 kV switchgear combines adjustable PtG pickup, bright local indication (LED + flag), multiple reset modes, and an IP65 enclosure; a PRO version adds serial communications. Itโ€™s a practical example to reference when drafting specifications.